냉방부하 저감을 위한 스마트 스킨의 에너지 성능 평가에 관한 연구
The objective of this study was to evaluate and analyze energy performance using TRNSYS 18 for smart skin and typical windows. The results are as follows : The base model for smart skin types in Seoul area was 24% to 37.6%, and the demonstration model was 14.6% to 25.5%, which reduced energy as comp...
Saved in:
Published in | 설비공학 논문집, 30(11) Vol. 30; no. 11; pp. 546 - 557 |
---|---|
Main Authors | , |
Format | Journal Article |
Language | Korean |
Published |
대한설비공학회
01.11.2018
|
Subjects | |
Online Access | Get full text |
ISSN | 1229-6422 2465-7611 |
DOI | 10.6110/KJACR.2018.30.11.546 |
Cover
Summary: | The objective of this study was to evaluate and analyze energy performance using TRNSYS 18 for smart skin and typical windows. The results are as follows : The base model for smart skin types in Seoul area was 24% to 37.6%, and the demonstration model was 14.6% to 25.5%, which reduced energy as compared to the target. Also, the reference model in Gwangju was 26.6% to 41.3%, and the demonstration model was 16.0% to 27.4%, which also reduced energy as compared to the target. The base model in the Seoul area was 108.8% to -35.5% and the demonstration model was 105.5% to -25.2%. In addition, the base model in Gwangju was 106.7% to -40.9% and the demonstration model 103.3% to -27.4%, which increased and reduced energy compared to the target. A smart skin and typical type, base model and demonstration model, and energy requirements in Seoul and Gwangju were reduced as the overall u-value was lower. On the other hand, 0.76 (W/㎡․K) showed higher energy consumption than 1.07 (W/㎡․K). In conclusion, energy savings in work facilities are high when the thermal perfusion rate is 1.07 (W/㎡․K). KCI Citation Count: 5 |
---|---|
Bibliography: | http://journal.auric.kr/kjacr |
ISSN: | 1229-6422 2465-7611 |
DOI: | 10.6110/KJACR.2018.30.11.546 |