배전계통에 초전도한류기 적용시 OCR 및 Recloser 동작특성 분석
In this paper, the method of protective coordination is studied to install Superconducting Fault Current Limiter (SFCL) to power distribution system. If SFCL is installed, the protective coordination is not operated well because of the decreased fault current. Thus, the resetting method of protectiv...
Saved in:
Published in | 전기학회 논문지 P권, 61(4) Vol. 61; no. 4; pp. 214 - 219 |
---|---|
Main Author | |
Format | Journal Article |
Language | Korean |
Published |
대한전기학회
2012
|
Subjects | |
Online Access | Get full text |
ISSN | 1229-800X 2586-7792 |
DOI | 10.5370/KIEEP.2012.61.4.214 |
Cover
Summary: | In this paper, the method of protective coordination is studied to install Superconducting Fault Current Limiter (SFCL) to power distribution system. If SFCL is installed, the protective coordination is not operated well because of the decreased fault current. Thus, the resetting method of protective devices is presented to coordinate protection system in power distribution system with resistor-type SFCL. The presented methods are divided into three parts; OCR, OCR-Recloser, OCR-Recloser-Recloser. The presented methods are proved through case studies using PSCAD/EMTDC simulation. |
---|---|
Bibliography: | KISTI1.1003/JNL.JAKO201236135724442 G704-001568.2012.61.4.010 |
ISSN: | 1229-800X 2586-7792 |
DOI: | 10.5370/KIEEP.2012.61.4.214 |