컴팩트형 VAV 공조기의 성능평가와 경제성 분석에 관한 연구

Ceiling cooling and heating system that consider load arrangement and space in the ceiling needs to be developed. Therefore, experimental and economic changes were done to verify the performance of compact type VAV. The test results were as follow. 1) Noise test result, measuring approximately 50.4...

Full description

Saved in:
Bibliographic Details
Published in설비공학 논문집, 27(1) Vol. 27; no. 1; pp. 44 - 49
Main Authors 김동철(Dong-Cheol Kim), 정광섭(Kwang-Seop Chung), 김영일(Young Il Kim)
Format Journal Article
LanguageKorean
Published 대한설비공학회 2015
Subjects
Online AccessGet full text
ISSN1229-6422
2465-7611
DOI10.6110/KJACR.2015.27.1.044

Cover

More Information
Summary:Ceiling cooling and heating system that consider load arrangement and space in the ceiling needs to be developed. Therefore, experimental and economic changes were done to verify the performance of compact type VAV. The test results were as follow. 1) Noise test result, measuring approximately 50.4 dB~56.6 dB (before ceiling in landfill), had a better ceiling deadline than the current measure, about a 10 dB noise reduction, so that the office baseline (40~50 dB) noise was judged to be less than test. 2) For the static pressure test result, taking out an outside hydrostatic 25 mmAq, 24.8 mmAq was measured, respectively, at the point. 3) For the life-cycle cost analysis result, the initial investment cost, maintenance replacement costs, and maintenance costs increased 0.2%, but the energy savings ratio was 19.5% while the whole life cycle savings of 40 years LCC was reduced 11.9%.
Bibliography:KISTI1.1003/JNL.JAKO201505458145372
http://www.sarek.or.kr
G704-000168.2015.27.1.003
ISSN:1229-6422
2465-7611
DOI:10.6110/KJACR.2015.27.1.044