열매체유 유동층 열교환기의 전열성능에 대한 실험적 연구

The heat transfer performance of heating medium oil fluidized bed heat exchanger was measured. The operation variables were air flow rate, air inlet temperature, moisture content, water flow rate and water inlet temperature. The outside heat transfer coefficient was determined from the heat exchange...

Full description

Saved in:
Bibliographic Details
Published in설비공학 논문집, 27(3) Vol. 27; no. 3; pp. 146 - 151
Main Authors 박상일(Sang-il Park), 고창복(Chang-Bok Ko), 이영수(Young-Soo Lee)
Format Journal Article
LanguageKorean
Published 대한설비공학회 2015
Subjects
Online AccessGet full text
ISSN1229-6422
2465-7611
DOI10.6110/KJACR.2015.27.3.146

Cover

More Information
Summary:The heat transfer performance of heating medium oil fluidized bed heat exchanger was measured. The operation variables were air flow rate, air inlet temperature, moisture content, water flow rate and water inlet temperature. The outside heat transfer coefficient was determined from the heat exchanger experiment and its experimental correlation was determined as a function of air velocity and viscosity of heating medium oil. Effect of viscosity was well agreed with the previous studies. Errors of the correlation equation was less than about 10% for outside heat transfer coefficient developed in this study when compared with the measured value. Hot water with the temperature greater than $77^{\circ}C$ could be produced by using the heating medium oil fluidized bed heat exchanger.
Bibliography:KISTI1.1003/JNL.JAKO201509364589217
http://www.sarek.or.kr/
G704-000168.2015.27.3.005
ISSN:1229-6422
2465-7611
DOI:10.6110/KJACR.2015.27.3.146