온도차 자연환기 이론의 유량계수에 대한 연구

This study reviews the discharge coefficient for thermal buoyancy natural ventilation through experimentation. We measure the air velocity at the outlet, which is needed to derive the discharge coefficient and to compare with the theoretical value. When a temperature difference exists between the in...

Full description

Saved in:
Bibliographic Details
Published in설비공학 논문집, 27(12) Vol. 27; no. 12; pp. 639 - 644
Main Authors 신동신(Dongshin Shin), 고현준(Hyunjun Ko), 김세형(Sehyung Kim), 선지형(Jihyung Seon), 윤상민(Sangmin Yoon), 이진영(Jinyoung Lee)
Format Journal Article
LanguageKorean
Published 대한설비공학회 2015
Subjects
Online AccessGet full text
ISSN1229-6422
2465-7611
DOI10.6110/KJACR.2015.27.12.639

Cover

More Information
Summary:This study reviews the discharge coefficient for thermal buoyancy natural ventilation through experimentation. We measure the air velocity at the outlet, which is needed to derive the discharge coefficient and to compare with the theoretical value. When a temperature difference exists between the inside and outside of the building, the measured discharge coefficient differs from the theoretical value with a maximum difference of 12%. The size and position of the openings have little effect on the discharge coefficient. For practical application, the theoretical discharge coefficient can be used with little modification.
Bibliography:KISTI1.1003/JNL.JAKO201505555187651
G704-000168.2015.27.12.006
http://journal.auric.kr/kjacr
ISSN:1229-6422
2465-7611
DOI:10.6110/KJACR.2015.27.12.639