Distance protection performance under single phase to Earth fault alone and simultaneously with open conductor failure

This paper presents performance of distance protection for overhead power line under a single phase earth fault alone and such fault simultaneously with an open conductor failure. The analysis is focused on steady state measurement of the fault-loop impedance and its placement in relation to distanc...

Full description

Saved in:
Bibliographic Details
Published in2016 Electric Power Networks (EPNet) pp. 1 - 5
Main Authors Smetek, Gabriela, Izykowski, Jan
Format Conference Proceeding
LanguageEnglish
Published IEEE 01.09.2016
Subjects
Online AccessGet full text
DOI10.1109/EPNET.2016.7999374

Cover

More Information
Summary:This paper presents performance of distance protection for overhead power line under a single phase earth fault alone and such fault simultaneously with an open conductor failure. The analysis is focused on steady state measurement of the fault-loop impedance and its placement in relation to distance protection first zone of MHO type. The considerations are based on using the fault data obtained from ATP-EMTP simulation of power line faults of different specifications. The sample results of the analysis are included and discussed.