Predictive pre-cooling of thermo-active building systems with low-lift chillers

This article describes the development and experimental validation of a data-driven model predictive control algorithm that optimizes the operation of a low-lift chiller, a variable-capacity chiller run at low pressure ratios, serving a single zone with a thermo-active building system. The predictiv...

Full description

Saved in:
Bibliographic Details
Published inHVAC&R research Vol. 18; no. 5; pp. 858 - 873
Main Authors Gayeski, N. T., Armstrong, P. R., Norford, L. K.
Format Journal Article
LanguageEnglish
Published Atlanta Taylor & Francis Group 01.10.2012
Taylor & Francis Ltd
Subjects
Online AccessGet full text
ISSN1078-9669
2374-4731
1938-5587
2374-474X
DOI10.1080/10789669.2012.643752

Cover

More Information
Summary:This article describes the development and experimental validation of a data-driven model predictive control algorithm that optimizes the operation of a low-lift chiller, a variable-capacity chiller run at low pressure ratios, serving a single zone with a thermo-active building system. The predictive control algorithm incorporates new elements lacking in previous chiller pre-cooling control optimization methods, including a model of temperature and load-dependent chiller performance extending to low-pressure and part-load ratios and a data-driven zone temperature response model that accounts for the transient thermal response of a concrete-core radiant floor thermo-active building system. Data-driven models of zone and concrete-core thermal response are identified from monitored zone temperature and thermal load data and combined with an empirical model of a low-lift chiller to implement model predictive control. The energy consumption of the cooling system, including the chiller compressor, condenser fan, and chilled-water pump energy, is minimized over a 24-h look-ahead moving horizon using the thermo-active building system for thermal storage and radiant distribution. A generalized pattern-search optimization over compressor speed is performed to identify optimal chiller control schedules at every hour, thereby accomplishing load shifting, efficient part-load operation, and cooling energy savings. Results from testing the system's sensible cooling efficiency in an experimental test chamber subject to the typical summer week of two climates, Atlanta, GA, and Phoenix, AZ, show sensible cooling energy savings of 25% and 19%, respectively, relative to a high efficiency, variable-speed split-system air conditioner.
Bibliography:ObjectType-Article-1
SourceType-Scholarly Journals-1
ObjectType-Feature-2
content type line 14
ObjectType-Article-2
ObjectType-Feature-1
content type line 23
ISSN:1078-9669
2374-4731
1938-5587
2374-474X
DOI:10.1080/10789669.2012.643752