UHF Measurement in Power Transformers: An Algorithm to Optimize Accuracy of Arrival Time Detection and PD Localization

Partial discharges (PDs) are among the various indicators that are utilized for monitoring of power transformers. PDs emit electromagnetic waves that can be received by inserting ultrahigh frequency probes inside the transformer tank, thus an advantage of this method is its higher robustness against...

Full description

Saved in:
Bibliographic Details
Published inIEEE transactions on power delivery Vol. 34; no. 4; pp. 1530 - 1539
Main Authors Ariannik, Mohamadreza, Azirani, Mohammad Akbari, Werle, Peter, Azirani, Asghar Akbari
Format Journal Article
LanguageEnglish
Published New York IEEE 01.08.2019
The Institute of Electrical and Electronics Engineers, Inc. (IEEE)
Subjects
Online AccessGet full text
ISSN0885-8977
1937-4208
DOI10.1109/TPWRD.2019.2909706

Cover

More Information
Summary:Partial discharges (PDs) are among the various indicators that are utilized for monitoring of power transformers. PDs emit electromagnetic waves that can be received by inserting ultrahigh frequency probes inside the transformer tank, thus an advantage of this method is its higher robustness against external noises. In this contribution, an algorithm is proposed to localize PDs in power transformers by capturing and analyzing multiple signal sets. Detecting exact arrival times (ATs) of a signal set is a challenging task in the PD localization. Different AT detection methods are applied to several signal sets to compare their effectiveness. Furthermore, modifications are introduced to enhance the precision of the AT detection. A fraction of the analyzed signal sets provide acceptable coordinates for the PD location. The localization algorithm consists of two approaches including wavelet denoising and AT sequence determination to eliminate PD coordinates that lie significantly far from the real location of the PD. The rest of the PD coordinates are then divided into two sections using a clustering method, and the center of the favorable cluster yields the definite PD coordinates. Precision of the PD localization algorithm is validated by three measurements inside a specially designed transformer tank.
Bibliography:ObjectType-Article-1
SourceType-Scholarly Journals-1
ObjectType-Feature-2
content type line 14
ISSN:0885-8977
1937-4208
DOI:10.1109/TPWRD.2019.2909706