Prediction Analysis on the Transport Distance of Supply Air in Warm Air Heating Room with Impinging Jet Ventilation Systems
To overcome the disadvantages of displacement ventilation( DV) and traditional mixing ventilation( MV) system,a new ventilation system known as impinging jet ventilation system( IJVS)has been developing. The warm air can be supplied with impinging jet ventilation( IJV), while the DV is only used for...
Saved in:
| Published in | 东华大学学报(英文版) Vol. 32; no. 5; pp. 725 - 730 |
|---|---|
| Main Author | |
| Format | Journal Article |
| Language | English |
| Published |
College of Environment Science and Engineering, Donghua University, Shanghai 201620, China
31.10.2015
|
| Subjects | |
| Online Access | Get full text |
| ISSN | 1672-5220 |
Cover
| Abstract | To overcome the disadvantages of displacement ventilation( DV) and traditional mixing ventilation( MV) system,a new ventilation system known as impinging jet ventilation system( IJVS)has been developing. The warm air can be supplied with impinging jet ventilation( IJV), while the DV is only used for cooling.However,the flow and temperature field of IJV under heating scenario has had few references. The paper is mainly focused on computational fluid dynamics( CFD) and developing an adequate correlation between the distance L that warm air can reach and different parameters in the warm IJVS by using response surface methodology( RSM). The results indicate that L decreases as the supply velocity υ decreases but increases as the supply temperature difference ΔT or the discharge height h decreases. In the variable air volume( VAV) system, it is necessary to determine supply parameters both under the maximum-heat-load condition and the small-heat-load condition. Unlike the VAV system,the constant air volume( CAV) system has no need to study the small-heat-load condition. Draught discomfort near the nozzle becomes the issue of concern in IJVS, thus the suitable discharge height is of great importance in design and can be calculated based on the predictive model. |
|---|---|
| AbstractList | To overcome the disadvantages of displacement ventilation( DV) and traditional mixing ventilation( MV) system,a new ventilation system known as impinging jet ventilation system( IJVS)has been developing. The warm air can be supplied with impinging jet ventilation( IJV), while the DV is only used for cooling.However,the flow and temperature field of IJV under heating scenario has had few references. The paper is mainly focused on computational fluid dynamics( CFD) and developing an adequate correlation between the distance L that warm air can reach and different parameters in the warm IJVS by using response surface methodology( RSM). The results indicate that L decreases as the supply velocity υ decreases but increases as the supply temperature difference ΔT or the discharge height h decreases. In the variable air volume( VAV) system, it is necessary to determine supply parameters both under the maximum-heat-load condition and the small-heat-load condition. Unlike the VAV system,the constant air volume( CAV) system has no need to study the small-heat-load condition. Draught discomfort near the nozzle becomes the issue of concern in IJVS, thus the suitable discharge height is of great importance in design and can be calculated based on the predictive model. |
| Author | 陈新秋 钟珂 卢思亮 亢燕铭 |
| AuthorAffiliation | College of Environment Science and Engineering, Donghua University, Shanghai 201620, China |
| AuthorAffiliation_xml | – name: College of Environment Science and Engineering, Donghua University, Shanghai 201620, China |
| Author_xml | – sequence: 1 fullname: 陈新秋 钟珂 卢思亮 亢燕铭 |
| BookMark | eNotT01PwzAU62FIjLH_EHHjUClJm6Q9TuNjQ5NAbMCxStvXNlOblCTTVvHnKRvvYsuy_OybYKKNhkkwJVzQkFGKr4O5c3s8Hqcixuk0-HmzUKrCK6PRQst2cMqhkfsG0M5K7XpjPXpQzktdADIV2h76vh3QQlmkNPqStjvzFUivdI3ejenQUfkGrbt-FP60F_DoE7RXrTw_2g7OQ-dug6tKtg7m_zgLPp4ed8tVuHl9Xi8Xm7AgEWEhTfHYnQhOC1ERDDKBXBaMc5IAroSICyEjIpKEs0RWaSx4FJeQ5ywCztMYollwf8k9Sl1JXWd7c7DjVpeVTXk65RlQTBhmGLPRe3fxFo3R9ffYPuut6qQdMs6FYIwkNPoF-p5oug |
| ClassificationCodes | TU831.3 |
| ContentType | Journal Article |
| Copyright | Copyright © Wanfang Data Co. Ltd. All Rights Reserved. |
| Copyright_xml | – notice: Copyright © Wanfang Data Co. Ltd. All Rights Reserved. |
| DBID | 2RA 92L CQIGP ~WA 2B. 4A8 92I 93N PSX TCJ |
| DatabaseName | 中文期刊服务平台 中文科技期刊数据库-CALIS站点 维普中文期刊数据库 中文科技期刊数据库- 镜像站点 Wanfang Data Journals - Hong Kong WANFANG Data Centre Wanfang Data Journals 万方数据期刊 - 香港版 China Online Journals (COJ) China Online Journals (COJ) |
| DatabaseTitleList | |
| DeliveryMethod | fulltext_linktorsrc |
| Discipline | Engineering |
| DocumentTitleAlternate | Prediction Analysis on the Transport Distance of Supply Air in Warm Air Heating Room with Impinging Jet Ventilation Systems |
| EndPage | 730 |
| ExternalDocumentID | dhdxxb_e201505005 667755182 |
| GrantInformation_xml | – fundername: National Natural Science Foundation of China; the Innovation Foundation of Shanghai Education Commission, China funderid: (51278094); (13ZZ054) |
| GroupedDBID | -02 -0B -SB -S~ 188 2B. 2C- 2RA 5VR 5XA 5XC 5XL 8RM 92D 92I 92L 92M 93E 93N 9D9 9DB ACGFS AFUIB ALMA_UNASSIGNED_HOLDINGS CAJEB CAJUS CCEZO CDRFL CHBEP CQIGP CW9 FA0 JUIAU Q-- R-B RT2 S.. T8R TCJ TGH TTC U1F U1G U5B U5L UGNYK UZ2 UZ4 ~WA 4A8 ABJNI ADMLS PSX |
| ID | FETCH-LOGICAL-c1315-2905221762c7f10ea8ebac56618e0f774c7a31788658af947634debb53e6694e3 |
| ISSN | 1672-5220 |
| IngestDate | Thu May 29 03:59:43 EDT 2025 Wed Feb 14 10:17:55 EST 2024 |
| IsPeerReviewed | true |
| IsScholarly | true |
| Issue | 5 |
| Keywords | warm air heating transport distance of supply air impinging jet ventilation systems (IJVSs) response surface methodology (RSM) |
| Language | English |
| LinkModel | OpenURL |
| MergedId | FETCHMERGED-LOGICAL-c1315-2905221762c7f10ea8ebac56618e0f774c7a31788658af947634debb53e6694e3 |
| Notes | CHEN Xin-qiu, ZHONG Ke, LU Si-liang, KANG Yan-ming 31-1920/N To overcome the disadvantages of displacement ventilation( DV) and traditional mixing ventilation( MV) system,a new ventilation system known as impinging jet ventilation system( IJVS)has been developing. The warm air can be supplied with impinging jet ventilation( IJV), while the DV is only used for cooling.However,the flow and temperature field of IJV under heating scenario has had few references. The paper is mainly focused on computational fluid dynamics( CFD) and developing an adequate correlation between the distance L that warm air can reach and different parameters in the warm IJVS by using response surface methodology( RSM). The results indicate that L decreases as the supply velocity υ decreases but increases as the supply temperature difference ΔT or the discharge height h decreases. In the variable air volume( VAV) system, it is necessary to determine supply parameters both under the maximum-heat-load condition and the small-heat-load condition. Unlike the VAV system,the constant air volume( CAV) system has no need to study the small-heat-load condition. Draught discomfort near the nozzle becomes the issue of concern in IJVS, thus the suitable discharge height is of great importance in design and can be calculated based on the predictive model. warm air heating;impinging jet ventilation systems(IJVSs);transport distance of supply air;response surface methodology(RSM) |
| PageCount | 6 |
| ParticipantIDs | wanfang_journals_dhdxxb_e201505005 chongqing_primary_667755182 |
| PublicationCentury | 2000 |
| PublicationDate | 2015-10-31 |
| PublicationDateYYYYMMDD | 2015-10-31 |
| PublicationDate_xml | – month: 10 year: 2015 text: 2015-10-31 day: 31 |
| PublicationDecade | 2010 |
| PublicationTitle | 东华大学学报(英文版) |
| PublicationTitleAlternate | Journal of Donghua University |
| PublicationTitle_FL | Journal of Donghua University(English Edition) |
| PublicationYear | 2015 |
| Publisher | College of Environment Science and Engineering, Donghua University, Shanghai 201620, China |
| Publisher_xml | – name: College of Environment Science and Engineering, Donghua University, Shanghai 201620, China |
| SSID | ssj0000627409 |
| Score | 1.9514431 |
| Snippet | To overcome the disadvantages of displacement ventilation( DV) and traditional mixing ventilation( MV) system,a new ventilation system known as impinging... |
| SourceID | wanfang chongqing |
| SourceType | Aggregation Database Publisher |
| StartPage | 725 |
| Title | Prediction Analysis on the Transport Distance of Supply Air in Warm Air Heating Room with Impinging Jet Ventilation Systems |
| URI | http://lib.cqvip.com/qk/86692X/201505/667755182.html https://d.wanfangdata.com.cn/periodical/dhdxxb-e201505005 |
| Volume | 32 |
| hasFullText | 1 |
| inHoldings | 1 |
| isFullTextHit | |
| isPrint | |
| journalDatabaseRights | – providerCode: PRVEBS databaseName: Inspec with Full Text issn: 1672-5220 databaseCode: ADMLS dateStart: 20091201 customDbUrl: isFulltext: true dateEnd: 99991231 titleUrlDefault: https://www.ebsco.com/products/research-databases/inspec-full-text omitProxy: false ssIdentifier: ssj0000627409 providerName: EBSCOhost |
| link | http://utb.summon.serialssolutions.com/2.0.0/link/0/eLvHCXMwnV3Nb9MwFLdKucAB8SnGAFkIn6KgfDiOc0zbjDK2grQVxqlKUmftoRkrrTTgj-Zf4D3HdTLBYXCJnmy3jf1-9fvwe8-EvK7mfljC5usGeSRcLqLSzblfulXJoyLkwqsCzB0-nojxlB-eRWe93q9O1NJ2U7wpf_w1r-R_uAptwFfMkv0HztovhQaggb_wBA7D80Y8_rjGYxbNwba4SBO3aIuWY33Njc4LwPQUvMPzu5MuMQjd-ZyvV5oeo-KIYXigRTee2XcrzKPCtkO1cT5hSFETNHetxLlRalnG2UCyZMiyiMkRkxkSKWdprIkRS0WHEEymLI1YdsAGQyYlyySTAzbwsSuBXvhUzGSiu5ox1lsxHGcT52xZu5fLrfV5jz9M3jrvLUKPps7J0kX3zbkVJymM-JLX7monqY2jw486EkLHG7WOlKzNAbRbIB4zdEo4NiZIfb7Y5p0QF-1RRkf8Il868Bsi8JrIBnNVuRECIkYDPfC6UqL1wrbn8HrLj5vEbaM9xOaU6XoN7_lifnVVzBROy4t0zd1boR_0ye10dHx0Yp2CWDOa67Ak-w5Y82MBE7mESenEsrqC9-_oQKf3yT1jvNC0QeID0lP1Q3K3sx6PyM8Wk3SHSQo0YJJaTNIdJulFRRtMUsAhXdYUMalpg0mKmKSISWoxSQGTtINJajD5mEwPstPh2DUXfLilHwKDg8SDKfogj8u48j2VS1XkJRgYvlReBYZJGeeg30oJanJeJRxkIZ-roohCJUTCVfiE9OuLWj0lFDTlxKu48uIi5yqQhVAVqLJclLIogljskX27jLOvTSGXmRBxjBUJgz3yyizszPy9v83-4NmzmwzaJ3da7D4n_c16q16A2ropXhpm_wYJpJW6 |
| linkProvider | EBSCOhost |
| openUrl | ctx_ver=Z39.88-2004&ctx_enc=info%3Aofi%2Fenc%3AUTF-8&rfr_id=info%3Asid%2Fsummon.serialssolutions.com&rft_val_fmt=info%3Aofi%2Ffmt%3Akev%3Amtx%3Ajournal&rft.genre=article&rft.atitle=Prediction+Analysis+on+the+Transport+Distance+of+Supply+Air+in+Warm+Air+Heating+Room+with+Impinging+Jet+Ventilation+Systems&rft.jtitle=%E4%B8%9C%E5%8D%8E%E5%A4%A7%E5%AD%A6%E5%AD%A6%E6%8A%A5%EF%BC%88%E8%8B%B1%E6%96%87%E7%89%88%EF%BC%89&rft.au=CHEN+Xin-qiu&rft.au=ZHONG+Ke&rft.au=LU+Si-liang&rft.au=KANG+Yan-ming&rft.date=2015-10-31&rft.pub=College+of+Environment+Science+and+Engineering%2C+Donghua+University%2C+Shanghai+201620%2C+China&rft.issn=1672-5220&rft.volume=32&rft.issue=5&rft.spage=725&rft.epage=730&rft.externalDocID=dhdxxb_e201505005 |
| thumbnail_s | http://utb.summon.serialssolutions.com/2.0.0/image/custom?url=http%3A%2F%2Fimage.cqvip.com%2Fvip1000%2Fqk%2F86692X%2F86692X.jpg http://utb.summon.serialssolutions.com/2.0.0/image/custom?url=http%3A%2F%2Fwww.wanfangdata.com.cn%2Fimages%2FPeriodicalImages%2Fdhdxxb-e%2Fdhdxxb-e.jpg |